The CSB issues safety recommendations to prevent the recurrence or reduce the likelihood or consequences of similar incidents or hazards in the future. Recommendations are issued to a variety of parties, including government entities, safety organizations, trade unions, trade associations, corporations, emergency response organizations, educational institutions, and public interest groups. Recommendations are published in CSB reports and are closed only by vote of the Board. The CSB tracks all recommendations and communicates regularly with recommendations recipients to ensure that the recommended corrective actions are implemented.

For more information, see Frequently Asked Questions about CSB recommendations.


Quick Search

 
Recommendations Status:
 
 
Expand All

Recommendations

Veolia Environmental Services Flammable Vapor Explosion and Fire (7 Recommendations)
Center for Chemical Process Safety (CCPS) (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: July 21, 2010

2009-10-I-OH-5

Revise control room siting guidelines to reflect the diversity of characteristics that Class 1B flammable liquids can exhibit (e.g., heavy vapor, and plant areas that provide congestion and confinement).


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Download

Environmental Technology Council (2 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: July 21, 2010

2009-10-I-OH-7

Supersedes 2007-01-I-NC-R3, issued pursuant to EQ Hazardous Waste Plant Explosions and Fire

Develop and issue standardized guidance for the processing, handling and storage of hazardous waste to reduce the likelihood of fires, explosions, and releases at hazardous waste treatment storage and disposal facilities. Include the incident findings, consequences, conclusions, and recommendations from the CSB investigations of the Environmental Quality facility and the Veolia ES Technical Solutions.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Recommendation Status Change Summary

2009-10-I-OH-6

Supersedes 2007-01-I-NC-R2, issued pursuant to EQ Hazardous Waste Plant Explosions and Fire

Petition the National Fire Protection Association, following the guidelines of their "Codes and Standards Development Process" (www.nfpa.org), to develop an occupancy standard specific to hazardous waste treatment, storage, and disposal facilities. The purpose of the standard would be to prescribe technical requirements for the safety to life and property from fire, explosion, and release; and to minimize the resulting damage from a fire, explosion, and release.
At a minimum, but not limited to, the standard should address:
• Hazard Identification
• Chemical Fire and Release Protection and Prevention
• Facility and Systems Design
• Employee Training and Procedures
• Inspection and Maintenance


Status: Closed - Acceptable Alternative Action
Closed - Acceptable Alternative Action (C - AAA)
 

PDF Document Recommendation Status Change Summary

National Fire Protection Association (NFPA) (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: July 21, 2010

2009-10-I-OH-4

Revise NFPA 30, Chapter 17, to include a section requiring a written engineering analysis to determine the safe separation distance for occupied buildings, control rooms, and operating areas. The analysis must be acceptable to the authority having jurisdiction.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Recommendation Status Change Summary

Veolia ES Technical Solutions (3 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: July 21, 2010

2009-10-I-OH-1

During the rebuild of the plant, revise policy to restrict occupancy of non-essential personnel in buildings in close proximity to operating plants.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Download

2009-10-I-OH-2

During the rebuild, design and install a closed relief system and develop a policy for safe venting (e.g., use of a flare) for relief systems to the atmosphere.


Status: Closed - Reconsidered/Superseded
Closed - Reconsidered/Superseded (C - R/S) - Recipient rejects the recommendation and also supports the rejection with a rationale with which the Board concurs. This designation may apply when later facts indicate that the concerns expressed in the recommendation were actually addressed prior to the incident, or when a recommendation is superseded by a new, more appropriate recommendation.
 

PDF Document Recommendation Status Change Summary

2009-10-I-OH-3

Conduct a process hazard analysis on all OSHA Process Safety Management covered processes to ensure all buildings and structures at the West Carrollton facility are located and designed in accordance with electrical classification and spacing as defined in NFPA 70.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Download