The CSB issues safety recommendations to prevent the recurrence or reduce the likelihood or consequences of similar incidents or hazards in the future. Recommendations are issued to a variety of parties, including government entities, safety organizations, trade unions, trade associations, corporations, emergency response organizations, educational institutions, and public interest groups. Recommendations are published in CSB reports and are closed only by vote of the Board. The CSB tracks all recommendations and communicates regularly with recommendations recipients to ensure that the recommended corrective actions are implemented.

For more information, see Frequently Asked Questions about CSB recommendations.


Quick Search

 
Recommendations Status:
 
 
Expand All

Recommendations

Bethune Point Wastewater Plant Explosion (13 Recommendations)
Camp Dresser & McKee Inc. (3 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: March 13, 2007

2006-3-I-FL-11

Revise CDM policies and procedures to ensure that appropriate quality control measures are applied so that designs specify appropriate materials and comply with applicable safety standards. Ensure that wastewater treatment plant design engineers are aware of the importance of proper material selection as well as the findings and recommendations of this report.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

2006-3-I-FL-12

Communicate the findings and recommendations of this report to all companies that contracted with CDM for methanol and other flammable liquid systems that were constructed with aboveground plastic pipe. Recommend replacing plastic pipe with an appropriate material in accordance with NFPA 30 and OSHA 1910.106.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

2006-3-I-FL-13

Communicate the findings and recommendations of this report to all companies that contracted with CDM for flammable liquid systems that included a flame arrester. Emphasize the importance of periodic maintenance of the flame arrester to ensure its effective performance.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

City of Daytona Beach (2 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: March 13, 2007

2006-3-I-FL-3

Adopt city ordinances to require departments to implement policies, practices, and procedures concerning safety and health in the workplace for city employees that are at least as effective as relevant OSHA standards. Emphasize compliance with chemical standards, including hot work procedures (OSHA Welding, Cutting, and Brazing Standard, Sections 1910.251 and 1910.252) and chemical hazard communication (OSHA Hazard Communication Standard 29 CFR 1910.1200). Implement procedures to ensure compliance with these policies, practices and procedures.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

2006-3-I-FL-4

Ensure that flammable liquid storage tanks used throughout the city comply with NFPA 30 and minimum federal standards in 29 CFR 1910.106, including appropriate piping and flame arresters.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

Governor and Legislature of the State of Florida (2 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: March 13, 2007

2006-3-I-FL-1

Enact legislation requiring state agencies and each political subdivision (i.e. counties and municipalities) of Florida to implement policies, practices, procedures, including chemical hazards covering the workplace health and safety of Florida public employees that are at least as effective as OSHA. Establish and fund a mechanism to ensure compliance with these standards. Consider legislation providing coverage of Florida public employees under an occupational safety and health program in accordance with Section 18(b) of the Occupational Safety and Health Act of 1970, and Code of Federal Regulations 29 CFR 1956.1.


Status: Closed - Unacceptable Action/No Response Received
Closed - Unacceptable Action/No Response Received (C - UA/NRR) - Recipient responds by expressing disagreement with the need outlined in the recommendation and the Board concludes that further correspondence on, or discussion of, the matter would not change the recipient?s position.
 

2006-3-I-FL-2

Develop and fund a workplace safety and health consultation program for Florida public employees similar to the private sector program currently administered by the Florida Safety Consultation Program at the University of South Florida.


Status: Closed - Unacceptable Action/No Response Received
Closed - Unacceptable Action/No Response Received (C - UA/NRR) - Recipient responds by expressing disagreement with the need outlined in the recommendation and the Board concludes that further correspondence on, or discussion of, the matter would not change the recipient?s position.
 

Methanol Institute (2 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: March 13, 2007

2006-3-I-FL-9

Work with the Water Environment Federation to prepare and distribute a technical bulletin containing information on the safe receipt, storage, use, and dispensing of methanol in wastewater treatment plants. In addition, include information on basic fire and explosion prevention measures when using bulk methanol (e.g., flame arrester maintenance, hot work programs, electrical classification).


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

2006-3-I-FL-10

Work with the Water Environment Federation to prepare safety training materials for wastewater treatment facilities that use methanol.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

National Fire Protection Association (NFPA) (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: March 13, 2007

2006-3-I-FL-5

Revise NFPA 30 to specifically exclude the use of thermoplastics in aboveground flammable liquid service.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Recommendation Status Change Summary

Occupational Safety and Health Administration (OSHA) (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: March 13, 2007

2006-3-I-FL-6

Revise 29 CFR 1910.106 to specifically exclude the use of thermoplastics in above ground flammable liquid service.


Status: Closed - Reconsidered/Superseded
Closed - Reconsidered/Superseded (C - R/S) - Recipient rejects the recommendation and also supports the rejection with a rationale with which the Board concurs. This designation may apply when later facts indicate that the concerns expressed in the recommendation were actually addressed prior to the incident, or when a recommendation is superseded by a new, more appropriate recommendation.
 

PDF Document Recommendation Status Change Summary

Water Environment Federation (2 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: March 13, 2007

2006-3-I-FL-7

Work with the Methanol Institute to prepare and distribute a technical bulletin containing information on the safe receipt, storage, use, and dispensing of methanol in wastewater treatment plants. In addition, include information on basic fire and explosion prevention measures when using bulk methanol (e.g., flame arrester maintenance, hot work programs, electrical classification).


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Recommendation Status Change Summary

2006-3-I-FL-8

Work with the Methanol Institute to prepare safety training materials for wastewater treatment facilities that use methanol.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.