The CSB issues safety recommendations to prevent the recurrence or reduce the likelihood or consequences of similar incidents or hazards in the future. Recommendations are issued to a variety of parties, including government entities, safety organizations, trade unions, trade associations, corporations, emergency response organizations, educational institutions, and public interest groups. Recommendations are published in CSB reports and are closed only by vote of the Board. The CSB tracks all recommendations and communicates regularly with recommendations recipients to ensure that the recommended corrective actions are implemented.

For more information, see Frequently Asked Questions about CSB recommendations.


Quick Search

 
Recommendations Status:
 
 
Expand All

Recommendations

Oil Tank Safety Study (6 Recommendations)
American Petroleum Institute (API) (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: October 27, 2011

2011-H-1-5

Create a new standard or amend existing standards covering exploration and production facilities to:

a) Warn that storage tanks at unmanned facilities may be subject to tampering or introduction of ignition sources by members of the public, which could result in a tank explosion or other accidental release to the environment.

b) Recommend the use inherently safer storage tank design features to reduce the likelihood of explosions, including restrictions on the use of open vents for flammable hydrocarbons, flame arrestors, pressure vacuum vent valves, floating roofs, vapor recovery systems or an equivalent alternative.

c) Require security measures at least as protective as API 2610 to prevent non-employee access to flammable storage tanks at upstream E&P sites, including such measures as a full fence surrounding the tank(s) with a locked gate, hatch locks on tank manways, and barriers securely attached to tank external ladders or stairways.

d) Require that hazard signs or placards be displayed on or near tanks to identify the fire and explosion hazards using words and symbols recognizable by the general public.

e) Recommend that new or revised mineral leasing agreements include security and signage requirements as described above.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Recommendations Status Change Summary

Environmental Protection Agency (EPA) (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: October 27, 2011

2011-H-1-1

Publish a safety alert directed to owners and operators of exploration and production facilities with flammable storage tanks, advising them of their general duty clause responsibilities for accident prevention under the Clean Air Act. At a minimum, the safety alert should:

a. Warn that storage tanks at unmanned facilities may be subject to tampering or introduction of ignition sources by members of the public, which could result in a tank explosion or other accidental release to the environment

b. Recommend the use of inherently safer storage tank design features to reduce the likelihood of explosions, including restrictions on the use of open vents for flammable hydrocarbons, flame arrestors, pressure vacuum vent valves, floating roofs, vapor recovery systems or an equivalent alternative.

c. Describe sufficient security measures to prevent non-employee access to flammable storage tanks, including such measures as a full fence surrounding the tank with locked gate, hatch locks on tank manways, and barriers securely attached to tank external ladders or stairways

d. Recommend that hazard signs or placards be displayed on or near tanks to identify the fire and
explosion hazards using words and symbols recognizable by the general public


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Recommendation Status Change Summary

Mississippi State Oil & Gas Board (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: October 27, 2011

2011-H-1-2

Amend state oil and gas regulations to require the use of inherently safer tank design features such as flame arrestors, pressure vacuum vents, floating roofs, vapor recovery systems or an equivalent alternative, to prevent the ignition of a flammable atmosphere inside the tank.


Status: Closed - Unacceptable Action/No Response Received
Closed - Unacceptable Action/No Response Received (C - UA/NRR) - Recipient responds by expressing disagreement with the need outlined in the recommendation and the Board concludes that further correspondence on, or discussion of, the matter would not change the recipient?s position.
 

National Fire Protection Association (NFPA) (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: October 27, 2011

2011-H-1-6

Amend NFPA 30, “Storage of Liquids in Tanks—Requirements for all Storage Tanks” as follows:
a) Remove the term “isolated” from the current wording of the standard and replace it with a more descriptive term, such as “normally unoccupied”

a) Remove the words “Where necessary” from Security for Unsupervised Storage Tanks, Chapter 21.7.2.2.

b) Add a reference to a relevant security standard that offers specifications on fencing, locks and other site security measures.

c) Add a definition of security encompassing requirements such as fencing, locked gates, hatch locks,and barriers.


Status: Closed - Acceptable Alternative Action
Closed - Acceptable Alternative Action (C - AAA)
 

PDF Document Recommendation Status Change Summary

State of Oklahoma/Oklahoma Corporation Commission (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: October 27, 2011

2011-H-1-3

Amend state oil and gas regulations to:

a) Protect storage tanks at exploration and production sites from public access by requiring sufficient security measures, such as full fencing with a locked gate, hatch locks on tank manways, and barriers securely attached to tank external ladders and stairways.

b) Require hazards signs or placards on or near tanks that identify the fire and explosion hazards using words and symbols recognizable by the general public.

c) Require the use of inherently safer tank design features such as flame arrestors, pressure vacuum vents, floating roofs, vapor recovery systems or an equivalent alternative, to prevent the ignition of a flammable atmosphere inside the tank.


Status: Closed - Unacceptable Action/No Response Received
Closed - Unacceptable Action/No Response Received (C - UA/NRR) - Recipient responds by expressing disagreement with the need outlined in the recommendation and the Board concludes that further correspondence on, or discussion of, the matter would not change the recipient?s position.
 

PDF Document Recommendation Status Change Summary

Texas Railroad Commission (RRC) (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: October 27, 2011

2011-H-1-4

Amend state oil and gas regulations to:

a) Protect storage tanks at exploration and production sites from public access by requiring sufficient security measures, such as full fencing with a locked gate, hatch locks on tank manways, and barriers securely attached to tank external ladders and stairways.

b) Require hazards signs or placards on or near tanks that identify the fire and explosion hazards using words and symbols recognizable to the general public.

c) Require the use of inherently safer tank design features such as flame arrestors, pressure vacuum vents, floating roofs, vapor recovery systems or an equivalent alternative to prevent the ignition of a flammable atmosphere inside the tank.


Status: Closed - Unacceptable Action/No Response Received
Closed - Unacceptable Action/No Response Received (C - UA/NRR) - Recipient responds by expressing disagreement with the need outlined in the recommendation and the Board concludes that further correspondence on, or discussion of, the matter would not change the recipient?s position.
 

PDF Document Recommendation Status Change Summary